1.功率因数0.2到0.9之间的补偿电容量:
C(uF) 补偿前cosQ1 Cos78o = 0.20 Cos77o = 0.22 Cos76o = 0.24 Cos75o = 0.26 oCos74 = 0.28 Cos73o = 0.30 oCos72 = 0.31 Cos71o = 0.33 Cos70o = 0.34 Cos69o = 0.36 Cos68o = 0.37 oCos67 = 0.39 Cos66o = 0.41 Cos65o = 0.42 Coso = 0.44 Cos63o = 0.45 Cos62o = 0.47 Cos61o = 0.48 oCos60 = 0.50 Cos59o = 0.52 Cos58o = 0.53 Cos57o = 0. Cos56o = 0.56 Cos55o = 0.57 Coso = 0.59 oCos53 = 0.60 Cos52o = 0.62 Cos51o = 0.63 oCos50 = 0. Cos49o = 0.66 oCos48 = 0.67 Cos47o = 0.68 oCos46 = 0.69 Cos45o = 0.70 Cos44o = 0.72 补偿后 cosQ= 0.9 Cos43o = 0.73 Cos42o = 0.74 oCos41 = 0.75 Cos40o = 0.76 oCos39 = 0.77 Cos38o = 0.78 Cos37o = 0.79 Cos36o = 0.80 Cos35o = 0.81 oCos34 = 0.82 Cos33o = 0.83 Cos32o = 0.84 Cos31o = 0.85 Cos30o = 0.86 Cos29o = 0.87 Cos28o = 0.88 oCos27 = 0.
2.运用PLC输出点以及输出点上所接电容组合实现上述电容量:
输出点 1 2 3 4 5 6 7 8 9 10 11 12 所接电 容(uF) 输出点 13 14 15 16 17 18 19 20 21 22 23 24 所接电 容(uF)
3.所需投入的组合电容对应的输出点数
补偿电容C(uF) 所需投入的组合电容对应的输出点数 7(或8) 7(或8)+9 7+8+9 10 7(或8)+10 7+8+10 11 7(或8)+11 7+8+11 12 7(或8)+12 7+8+12 13 7(或8)+13 7+8+13 14 7(或8)+14 7+8+14 15 7(或8)+15 7+8+15 16 7(或8)+16 6+7(或8)+16 17 7(或8)+17 6+7(或8)+17 18 5+18 5+6+18 19 5+19 5+6+19 20 5+20 4+5+20 21 4+21 3+4+21 22 3+22 3+4+22 23 3+23 2+3+23
24 2+24 1+2+24 4. 互感器
(1)电流互感器
根据本课题的参数,额定工作电压:50HZ,AC220;输入电流≤ 50A,由于PLC装置的电流是2A,分析后选择LMZJ1-0.5型电流互感器,电流比为50A/5A,穿心匝数为3。 (2)电压互感器
根据本课题的参数,额定工作电压:50HZ,AC220;输入电流≤ 50A,由于选用的PLC装置的电压是24V,分析后选择选择JDZ3-1 380/100电压互感器。 5.互感器