第28卷第6期 2014年11月 发电没备 P0WER EQUIPMENT Vol_28,NO.6 NOV.2014 闭式冷却水板式换热器的应用与维护 孟铭强 ,张乐福 ,韩光辉。,秦博杰 (1.上海交通大学机械与动力工程学院,上海200030; 2.中核核电运行管理有限公司,浙江海盐314300) 摘要:结合秦山第二核电厂闭式冷却水换热器选用的实例,介绍了板式换热器的结构,以及运行中因 海水含泥沙量大,板片容易在海水人口和出口处发生磨损穿孔的情况。通过对发生穿孔的原因进行分析,提 出了破损板片的修补方案,对板式换热器在电厂的应用和维护提出了建议。 关键词:核电厂;板式换热器;磨损;维护 中图分类号:TM623;TK172 文献标志码:A 文章编号:1671 086X(2014)06—0435—03 Application and Maintenance of Plate Heat Exchanger with Closed Cooling Water Meng Mingqiang ,Zhang Lefu ,Han Guanghui ,Oin Bojie (1.School of Mechanical Engineering,Shanghai Jiaotong University,Shanghai 200030,China; 2.CNNC Nuclear Power Operation&Management Co.,Ltd.,Haiyan 314300,Zhejiang Province,China) Abstract:Taking the heat exchanger applied in Qinshan Phase II Nuclear Power Plant as an example, an introduction is being presented to the structure of its plate heat exchanger,as well as to the wear failures frequently encountered at sea water inlet and outlet due to high sand content in sea water.By analyzing the wear causes,repair schemes are proposed for worn plates,and suggestions for application and maintenance of the plate heat exchanger are put forward simultaneously. Keywords:nuclear power station;plate heat exchanger;wear;maintenance 板式换热器与常规管壳式换热器相比,具有 结构紧凑、换热效率高、安装空间小、便于检修等 优点,广泛应用于电厂设备冷却水系统,实现闭 式冷却水与热井之间的换热。秦山第二核电厂 压紧板、活动压紧板、下导杆、上导杆和夹紧螺柱 等主要零部件组成(见图1)。 闭式冷却水换热器采用瑞典阿法拉伐M30板式 换热器,板片采用抗海水腐蚀的钛材制造。 板式换热器板片厚度较薄,由于海水中含有 泥沙,秦山第二核电厂板式换热器在运行中,存 在频繁穿孔泄漏问题,不仅增加了运行维护成 本,还严重影响了核电机组的运行。通过对板片 柱 穿孔的原因进行分析,笔者提出了破损板片的修 补方案,对板式换热器在电厂的应用和维护提出 了建议。 1板式换热器 1.1结构 固 板式换热器是由传热板片、密封垫片、固定 收稿日期:2014-02—18 图1板式换热器示意图 作者简介:孟铭强(1983 ),男,工程师,主要从事核电机械设备检修工作。 E—mail:mengmq@cnnp.corn.cn